DEPARTMENT OF LABOR MINE SAFETY AND HEALTH ADMINISTRATION Southeastern District Metal and Nonmetal Mine Safety and Health Accident Investigation Report Surface Nonmetal Mine Fatal Electrical Accident Kentucky Solite Corporation Kentucky Solite Corporation Brooks, Bullitt County, Kentucky Mine I.D. 15-00187 May 16, 1997 By James B. Daugherty Supervisory Mine Inspector Donald R. Baker Mine Safety and Health Inspector Terry G. Lingenfelter Mine Safety and Health Inspector(Electrical) Originating Office Mine Safety and Health Administration 135 Gemini Circle, Suite 212 Birmingham, Alabama 35209 Martin Rosta District Manager GENERAL INFORMATION Paul L. King, finish plant supervisor, age 40, was electrocuted at approximately 2:15 p.m. on May 16, 1997, when he came into contact with the metal casing of a water pump that was energized with 120 volts AC. The victim had 20 years experience at this mine, the last 16 as finish plant supervisor. Records indicated he had received annual refresher training in February 1997. Michael McHugh, chief supervisor for Kentucky Solite Corporation, notified the Birmingham, Alabama, district office of the accident at 3:30 p.m., on May 16, 1997. An investigation was started the same day. The Kentucky Solite Corporation, a multiple bench shale and clay operation, owned and operated by Kentucky Solite Corporation, was located off Highway 1020 in Brooks, Bullitt County, Kentucky. The principal operating official was Patrick Piazza, general plant manager. The mine normally worked one, 8-hour shift a day, 5 days a week and employed 46 persons. The material was drilled, blasted, crushed, and sized on site. It was then conveyed to stockpiles where it was sold as lightweight aggregate. The last regular inspection of this operation was conducted April 15-17, 1997. PHYSICAL FACTORS INVOLVED The accident occurred in the lower sump of the finish plant building. The sump was constructed of concrete and measured 12 feet wide, 18 feet long and 5 feet deep. The sump was accessed by a metal stairway. At the time of the accident, the sump contained approximately 10 inches of water. A 3 HP, 120 volt AC sump pump manufactured by the Zoeller Pump Company was located in the sump. Power for the pump was supplied from a wall outlet by two extension cords. The 120 volt AC outlet was located on the south wall of the first floor of the finish plant building and was protected by a 20 amp single pole circuit breaker located in a panel on the second floor electrical control room. Electrical metallic tubing was used as the grounding conductor from the panel to the outlet. One extension cord was an 18/3 AWG SO cord about 20 feet long and the other was a 16/3 AWG SO cord about 25 feet long. Both cords recently had new female ends installed. The extension cord nearest the sump pump was improperly wired by having the ground wire connected to the hot terminal, the hot wire connected to the neutral terminal and the neutral wire connected to the ground terminal. The extension cord plugged into the wall outlet had the hot wire connected to the neutral terminal and the neutral wire connected to the hot terminal resulting in reverse polarity. This configuration of the two extension cords caused the casing of the pump to be energized. DESCRIPTION OF ACCIDENT Paul L. King, victim, reported for work on May 16, 1997, at 6:00 a.m., his regular starting time. King proceeded with his normal duties as supervisor. About 1:00 p.m. he was observed walking toward the finish plant building. There were no witnesses to the accident. However, since employees stated that the pump was not in the sump earlier on the day of the accident, it is believed King put the pump in the sump and connected the power cords. Apparently when the pump failed to start, King went to check on it and was electrocuted. At approximately 3:15 p.m. Ernest Sparks, scalehouse operator went into the office and the secretary asked Sparks if King had gone home. Sparks said that King's personal vehicle was still in the parking lot and his office door was still open. At this time, several employees went into the plant area to look for King. Sparks went to the finish building and found King laying in the sump on his right side with his left foot on the bottom step of the metal stairway with his face under water. Sparks immediately disconnected the two extension cords going to the pump and called for help. Several employees went to the scene while Mike McHugh, chief supervisor called 911. The employees checked for vital signs but were unable to detect a pulse. The Bullitt County Sheriff's Department, emergency management service and County Coroner arrived on the scene about 3:40 p.m. The Coroner pronounced the victim dead at 3:45 p.m. and estimated the time of death to be about 2:15 p.m. The cause of death was electrocution. CONCLUSION The cause of the accident was improper repair to extension cords and failure to test the cords after repairs were made. VIOLATIONS Order No. 4554445 Issued on May 17, 1997, under the provisions of Section 103(k): Citation No. 4521026 Issued on May 20, 1997, under provisions of Section 104(a) of the Mine Act for violation of Standard 56.12028: |